| Model | GTQ-XP4000 |
| Measuring gas | Combustible gases (Methane, propane, isobutane, hydrogen, etc.) |
| Measuring type | Diffusion type |
| Measuring method | Infrared |
| Measuring Range | 0-100% LEL |
| Response time | < 30sec / 90% scale |
| Accuracy | ±3% / Full Scale |
| Operation mode display | Normal / High Alarm / Low Alarm / Trouble LED |
| Measuring value display | Digital tube |
| Power | 24V DC nominal, 18 to 31V DC |
| Alarm signal output | Light and sound output / 50mA |
| Output signal | XBUS 2/4 wire Optional expansion module: 4-20mA / RS485 / HART / NB-IoT / 4G / One-channel passive relay output / HBUS |
| Conduit connection | Standard: 3xM26x1.5P Option: FPT3/4', NPT3/4'' |
| Mounting type | Wall/Pole/Ceiling mount |
| Operating temperature | -40°C ~ +70°C |
| Operating humidity | 5 to 95% RH (Non-condensing) |
| Housing Material | Aluminum alloy |
| Dimensions | 157.5(W) x 178.4(H) x 90(D) mm |
| Explosion Proof | Ex db IIC T6 Gb |
| Certification | Refer to technical documentation |
| Sensor Type | Measuring Gas | Measuring Range | Operating Temp. | Typical Life | Response Time |
| Catalytic Type | Combustible gases | 0~100%LEL | -40°C ~ +70°C | 36 months | <15sec / 90% scale |
Output signal shows a good linear relationship with gas concentration, enabling precise concentration readings.
Minimal performance fluctuations during long-term use, ensuring reliable detection results.
Quickly captures gas concentration changes and triggers timely alerts.
Detects most flammable gases and flammable vapors (e.g., hydrogen (H₂), methane (CH₄), propane (C₃H₈), ethanol vapors, etc.).
Exhibits certain tolerance to common poisoning substances (e.g., silicon, lead compounds), with a long service life and low attrition rate.
A: The detector targets a wide range of combustible gases including Methane, Propane, Isobutane, Hydrogen, and other common flammable industrial gases and vapors.
A: The infrared detection principle delivers outstanding resistance to sensor poisoning from silicon, sulfur, and halogen compounds, dramatically increasing the sensor lifespan and lowering overall maintenance demands.
A: No. The GTQ-XP4000 is equipped with a digital sensor assembly designed to be hot-swapped and replaced quickly without requiring calibration in the field.
A: It features an integrated two-stage built-in sound-light alarm along with high-brightness digital tube and LED indicators to explicitly convey Normal, High/Low Alarm, or Trouble status.
A: The device offers a standard expansion port supporting 4-20mA, HART, RS485, NB-IoT, 4G, passive relay outputs, and XBUS/HBUS communication protocols for flexible system integration.
A: Yes, it is constructed with a robust IP66-rated aluminum alloy housing, explosion-proof class Ex db IIC T6 Gb, and operates reliably in extreme temperatures ranging from -40°C to +70°C.