As an upgraded version of the AT0503 series, the GTYQ-AT0503/d integrates real-time display functionality while retaining all core explosion-proof and detection performance. It adopts a full explosion and dust ignition proof structure, ensuring safe operation in locations with potential combustible gas leakage risks. The standard light and sound alarm interface supports on-site expansion, and the dual-wire wiring method simplifies installation for both new projects and retrofits.
The digital sensor assembly supports hot-swappable replacement without on-site calibration, ensuring continuous system operation. It supports both XBUS and 4-20mA analog communication, and is compatible with third-party 3/4-wire 4-20mA detectors for flexible system integration. The biggest highlight is its built-in LCD display, which presents real-time gas concentration values intuitively, helping operators monitor site status at a glance. With IP66 protection, it operates reliably in harsh environments. This model is suitable for industrial sites that require both remote transmission and on-site direct reading of gas data.
description2
| Parameter | Specification Details |
|---|---|
| Model | GTYQ-AT0503/d |
| Measuring gas | Combustible gases (Methane, propane, isobutane, hydrogen, etc.) |
| Measuring type | Diffusion type |
| Measuring method | Catalytic |
| Measuring Range | 0-100% LEL |
| Response time | < 15sec / 90% scale |
| Accuracy | ±3% / Full Scale |
| Operation mode display | Normal / Alarm / Trouble LED |
| Measuring value display | LCD / Rate flow |
| Power | 24V DC nominal, 18 to 31V DC |
| Alarm signal output | Light and sound output / 50mA |
| Output signal | XBUS 2/4 wire / Analog: 4-20mA |
| Conduit connection | Standard: 2xM26x1.5P Option: FPT3/4", NPT3/4" |
| Mounting type | Wall/Pole/Ceiling mount |
| Operating temperature | -40°C ~ +70°C |
| Operating humidity | 5 to 95% RH (Non-condensing) |
| Housing Material | Aluminum alloy |
| Dimensions | 150(W) x 151.5(H) x 74(D) mm |
| Explosion Proof | Ex db IIC T6 Gb |
| Certification | Refer to website |
| Sensor Type | Measuring Gas | Measuring Range | Operating Temperature | Typical Life | Response Time |
|---|---|---|---|---|---|
| Catalytic Type | Combustible gases | 0~100%LEL | -40°C ~ +70°C | 36 month | <15sec / 90% scale |
Output signal shows a good linear relationship with gas concentration, enabling precise concentration readings.
Minimal performance fluctuations during long-term use, ensuring reliable detection results.
Quickly captures gas concentration changes and triggers timely alerts.
Detects most flammable gases and flammable vapors (e.g., hydrogen (H₂), methane (CH₄), propane (C₃H₈), ethanol vapors, etc.).
Exhibits certain tolerance to common poisoning substances (e.g., silicon, lead compounds), with a long service life and low attrition rate.
The main upgrade is the built-in LCD display, which provides real-time on-site gas concentration readings, allowing operators to monitor target area safety levels at a glance while retaining all robust detection functionalities.
It is designed to measure combustible gases (such as methane, propane, isobutane, hydrogen, etc.) with a measuring range of 0~100% LEL, utilizing catalytic sensor technology.
No, the detector features a digital sensor assembly that supports hot-swappable replacement without the need for on-site calibration, facilitating uninterrupted system operation and simpler maintenance.
It supports both XBUS (2/4 wire) and 4-20mA analog output signals. Additionally, it is fully compatible with third-party 3/4-wire 4-20mA detectors for flexible system integration.
Yes. Built with a robust aluminum alloy housing rated at IP66 protection and configured with a full explosion and dust ignition proof structure (Ex db IIC T6 Gb), it operates reliably within temperatures ranging from -40°C to +70°C.